Purpose and Scope of the Standard
IS/IEC 61439 is a multi-part standard that defines the requirements for low-voltage switchgear and controlgear assemblies — commonly referred to as LV panels or LV boards. It covers the design, construction, testing and documentation of assemblies used in electrical distribution and motor control applications up to 1000 V AC. The standard applies to the assembly as a whole, not just to the individual components within it.
Assembly Manufacturer Responsibilities
The assembly manufacturer — the company that designs and builds the panel — is responsible for ensuring that the completed assembly meets the requirements of the standard. This includes selecting appropriate components, designing the enclosure and busbar system, verifying the assembly against the standard's requirements, and providing the documentation required to demonstrate compliance. The assembly manufacturer's responsibilities are distinct from those of the original manufacturer of the components used in the assembly.
Original Manufacturer and Assembly Manufacturer Concepts
The standard distinguishes between the original manufacturer — the company that designed and type-tested the original assembly design — and the assembly manufacturer — the company that builds assemblies based on that design. An assembly manufacturer may use type-tested components from an original manufacturer and build assemblies that comply with the standard without conducting all the type tests themselves, provided that the assembly is built within the verified design envelope of the original manufacturer.
Design Verification
Design verification confirms that the assembly design meets the requirements of the standard. It can be carried out by type testing — physically testing a representative assembly — or by calculation and comparison with a tested reference design. Design verification covers temperature rise, short-circuit withstand, dielectric properties, protection against electric shock, mechanical operation, degree of protection and other characteristics. Design verification is a one-time activity for a given design; it does not need to be repeated for every assembly built to that design.
Routine Verification
Routine verification is carried out on every completed assembly before it leaves the factory. It confirms that the assembly has been built correctly and that it meets the basic safety requirements. Routine verification typically includes inspection of the assembly, checking of wiring and connections, dielectric testing of the insulation, and functional testing of the control circuits. Routine verification results must be documented and provided to the purchaser.
Temperature-Rise Considerations
The standard defines maximum temperature-rise limits for busbars, terminals, accessible surfaces and components within the assembly. Temperature rise depends on the current carried, the enclosure design, the ventilation arrangement and the ambient temperature. The temperature-rise verification must be carried out at the maximum continuous current rating of the assembly. Exceeding the temperature-rise limits reduces the life of insulation and components and can create a fire risk.
Short-Circuit Withstand
The assembly must be capable of withstanding the prospective short-circuit current at the point of installation for the duration required to clear the fault. The short-circuit withstand is verified by type testing or by calculation. The rated short-circuit withstand current of the assembly must be equal to or greater than the prospective short-circuit current at the installation point, as determined by a fault-level study.
Degree of Protection
The degree of protection — expressed as an IP code — defines the level of protection provided by the enclosure against the ingress of solid objects and liquids. The required IP rating depends on the installation environment. The IP rating must be verified by testing or by reference to a tested enclosure design. The IP rating applies to the complete assembly, including access doors, cable entry points and ventilation openings.
Documentation and Traceability
The standard requires the assembly manufacturer to provide documentation that allows the assembly to be identified, maintained and modified. This includes the assembly rating plate, schematic diagrams, general arrangement drawings, a list of components with their ratings, and the routine verification test report. For assemblies used in regulated industries, additional documentation — material certificates, calibration records, qualification documents — may be required.
Questions Purchasers Should Ask
Purchasers of LV panels should ask: Is the assembly designed and built in accordance with IS/IEC 61439? What design verification method has been used — type testing or calculation? What is the rated short-circuit withstand current of the assembly, and how has it been verified? What routine verification tests are carried out on every assembly? What documentation will be provided with the assembly? Applicable verification and documentation depend on the approved assembly design, project specification and agreed scope.
Key Takeaways
- IS/IEC 61439 applies to the assembly as a whole, not just to the individual components within it.
- Design verification confirms the assembly design meets the standard — it is a one-time activity for a given design.
- Routine verification is carried out on every completed assembly before it leaves the factory.
- The rated short-circuit withstand current must be equal to or greater than the prospective fault current at the installation point.
- Applicable verification and documentation depend on the approved assembly design, project specification and agreed scope.